Description
Mitsubishi Heavy Industries SCM80ZS-W 8.0kW Outdoor Multi Unit
With the ability to connect 4 indoor units to a single outdoor unit, the SCM80ZS-W outdoor multi-split system offers a compact and versatile solution for cooling and heating multiple rooms. Thanks to improved component design, the SCM-ZS-W series boasts super quiet operation while also delivering high energy efferences. The ability to control each indoor unit independently offers even further energy savings while also providing complete control.
Key features
- Individual control over each room
- Energy efficient solution for multiple rooms
- Wide range of indoor units to suit any space
- Super quiet operation
| Outdoor | SCM80ZS-W | |||
| Power source (Outdoor) | 1 Phase 240V 50Hz | |||
|
*Operation data |
Nominal Capacity (Range) |
Cooling T1 |
kW |
8.0 (1.8~9.2) |
| Heating H1 | 9.3 (1.1~9.8) | |||
|
Power consumption |
Cooling T1 | 1.70 | ||
| Heating H1 | 1.95 | |||
|
Running current |
Cooling T1 |
A |
7.2 | |
| Heating H1 | 8.2 | |||
| Inrush current, maximum current | 5, 20 | |||
| EER | Cooling T1 | 4.71 | ||
| COP | Heating H1 | 4.77 | ||
|
Sound power level (JIS C9612) |
Cooling T1 |
dB(A) |
66 | |
| Heating H1 | 67 | |||
|
Sound pressure level (JIS C9612) |
Cooling T1 | 54 | ||
| Heating H1 | 54 | |||
|
Silent mode |
Cooling T1 | 46 | ||
| Heating H1 | 50 | |||
| External dimensions (HxWxD) | mm | 750×880(+73)x340 | ||
| Net weight |
kg |
61 | ||
|
Refrigerant (R32) |
Quantity | 2.55 | ||
| Pre charged to pipe length | m | 30 | ||
|
Installation data |
Refrigerant piping |
Liquid line |
mm |
Ø6.35 x 4 |
| Gas line | Ø9.52 x 4 | |||
| Connection method | Flare connection | |||
| Maximum pipe length to one indoor unit |
m |
25 | ||
| Total pipe length to all indoor units | 70 | |||
| Max vertical height diff. between O.U. and I.U. | 20 ( O.U. above I.U.) / 20 ( O.U. below I.U. ) | |||
|
Indoor Unit Combination |
SRK-ZSA-W |
kW |
2.0, 2.5, 3.5, 5.0 | |
| SRK-ZSXA-W | 2.0, 2.5, 3.5, 5.0, 6.0 | |||
| SRK-ZRA-W | 7.1 | |||
| SRF-ZS(X)-W | 2.5, 3.5, 5.0 | |||
| SRR-ZS-W | 2.5, 3.5, 5.0, 6.0 | |||
| FDTC-VH | 2.5, 3.5, 5.0, 6.0 | |||
| FDUM-VH | 5.0 | |||
| Indoor Unit Connection | 2 to 4 Units | |||
| Indoor Connection Capacity | kW | 8.0 to 13.5 | ||
|
Outdoor air temperature (upper, lower limits) |
Cooling | °C | -15 to 46 | |
| Heating | -15 to 24 | |||